Hopp over seksjon - Til hovedinnhold - Topp
123 - 550kV / 1250 - 4000 A
Each phase of the Mark 40 disconnectors has a vertical break with two fixed and one rotating isolator column. The disconnector is equipped with high tension point contacts with silver inlay. The unique construction clears any ice or corrosion coating on closing and opening. Design and craftmanship is according to IEC standards.
The framework is made from hot galvanised square profiles. The bearing for the rotating column is maintenance-free and consist of a stainless steel shaft with Tufcot supports and radial bearing. Tufcot is a laminated, polyester based, low friction material with Teflon. Conducting parts are made from high-grade aluminium alloys. The contacts have silver inlay, and moving parts have ball bearings that are corrosion free and without need for lubrication.
| Rated voltage | 123 | 145 | 170 | 245 | 300 | 362 | 420 |
| Lightning Impulse Withstand Voltage | |
||||||
| - to earth kV | 550 | 650 | 750 | 1050 | 1050 | 1175 | 1425 |
| - across the isolating distance kV | 630 | 750 | 860 | 1200 | 1050 | 1175 | 1425 |
| Power Frequency Withstand Voltage | |||||||
| - to earth kV | 230 | 275 | 325 | 460 | 460 | 460 | 520 |
| - across the isolating distance kV | 265 | 315 | 375 | 530 | 530 | 530 | 610 |
| Switching Impulse Withstand Voltage | |||||||
| - to earth kV | - | - | - | - | 850 | 950 | 1050 |
| - across the isolating distance kV | - | - | - | - | 700 | 800 | 900 |
| Current and Short circuit ratings |
1600A - 125kA peak - 50kA/2 sec. |
| Voltage (kV) | 123 | 145 | 170 | 245 | 300 | 362 | 420 |
| A B C D |
1220 1561 3956 1900 |
1500 1841 4536 2200 |
1700 2041 5036 2500 |
2300 2641 6373 3200 |
2650 2991 6686 3200 |
3150 3491 8186 4200 |
3350 3691 8386 4200 |

EB Elektro AS - Elektroveien 8 - N-3300 Hokksund - Tlf.: +47 32 25 01 20 - Fax: +47 32 25 01 21 - E-post: post@eb-elektro.no