• High tenstion point contacts
  • "Reversed loop design"
  • Self-cleaning and self-adjusting contacts
  • Low contact resistance
  • Minimal maintenance
  • Earthing switch can be mounted both sides
  • Corrosion-free and maintenance-free bearings

Hopp over seksjon - Til hovedinnhold - Topp

Til toppen av siden

Horisontal Center-Break Disconnectors

72,5 - 420kV / 1250 - 3150 A

The HCB disconnector has a flexible and modular design.  The construction, based on earlier designs, fulfills requirements for the most exposed conditions, and has shown its durability through many years of maintenance-free operation.  The HCB is tested according to IEC standards.  The disconnector has high tension point contacts.  The movement of the switch effectively clears the contacts of any ice and corrosion coating.

The framework is made from hot galvanised square profiles.  The bearing for the rotating isolator column is maintenance-free and consists of a stainless steel shaft with a Tufcot radial bearing.  Tufcot is a laminated, polyester based, low friction, material with Teflon.

The disconnector is supplied according to international standards.  Conducting parts are produced from high-grade aluminium alloys.

The contacts are made from silver-plated copper (Reversed loop design). A high and stable contact pressure is ensured through the use of springy contacts.





Technical Information

Rated voltage Ur (kV) 72.5 123 145 170 245 300 362 420
Lightning Impulse Withstand Voltage:                    
- to earth TE Ud (kV) 325 550 650 750 1050 1050 1175 1425
- across the isolating distance AID Ud (kV) 375 630 750 860 1200 1050 1175 1425
Power Frequency Withstand Voltage:                    
- to earth TE Ud (kV) 140 230 275 325 460 380 450 520
- across the isolating distance AID Ud (kV) 160 265 315 375 530 435 520 610
Switching Impulse Withstand Voltage:      
 

 

     
- to earth TE Up (kV) - - - - - 850 950 1050
- across the isolating distance AID Us (kV) - - - - - 700
(+245)
800
(+295)
900
(+345)
Current and Short circuit ratings     * 1600A – 100 kA peak – 40 kA/3 sec.
* 2500A – 100 kA peak – 40 kA/3 sec.
* 3150A – 100 kA peak – 40 kA/3 sec.
* 4000A – 100 kA peak – 40 kA/3 sec.

 

Voltage (kV) 72.5 123 145 170 245 300 362 420
A
B
C


770
1100 
1250
950 

1220
1550 
1700
1450

1500
1830 
1980
1650 

1700
2030 
2180
1900 

2300
2630
2835
2650
2650
2980
3130
2900
3150
3350

 

EB Elektro AS - Elektroveien 8 - N-3300 Hokksund - Tlf.: +47 32 25 01 20 - Fax: +47 32 25 01 21 - E-post: post@eb-elektro.no